Enclosed car park ventilation: how does a jet fan system work?

Ventilation14 November 2026Ekura Engineering

Ventilation in an enclosed car park does two jobs: every day it removes exhaust fumes, and in a fire it extracts smoke to keep escape routes and fire-fighting access visible. Jet fan systems do both without ductwork.

Enclosed basement car parks are part of almost every residential, office, shopping centre and hospital project. In these spaces, where natural ventilation is not enough, mechanical ventilation is essential for both health and fire safety. In recent years, ductless jet fan systems have become the most common solution.

Animated explainer · on-screen text in Turkish

Why is car park ventilation necessary?

Carbon monoxide (CO) and nitrogen oxides from vehicle exhausts can quickly reach harmful levels in an enclosed space. In daily operation, ventilation dilutes and removes these gases. In a fire, its role changes: smoke and hot gases are extracted in a controlled way so that users can leave the car park and the fire brigade can see their way to the fire.

What do the regulations say?

The Turkish Regulation on Fire Protection of Buildings sets the following basic requirements for enclosed car parks:

  • Enclosed car parks with a total area above 2,000 m² must have a mechanical smoke extraction system providing at least 10 air changes per hour.
  • Enclosed car parks above 600 m² must have an automatic sprinkler system, fire hose cabinets and a fire brigade inlet connection.
  • Enclosed car parks where vehicles are lifted by elevator must have natural or mechanical ventilation.
  • In car parks accessible to LPG vehicles, ventilation and electrical installations must be explosion-proof (ex-proof) and ventilation must be linked to a gas detector.

How does a jet fan system work?

In conventional car park ventilation, air is extracted through large ducts and grilles running along the ceiling. A jet fan system has no ducts. Small, high-velocity fans suspended from the ceiling give thrust to the air and move it from one end of the car park to the other, towards the exhaust shafts. The system has three main parts:

  • Jet fans: Installed at intervals on the ceiling, they push the air towards the extraction point.
  • Exhaust fans and shafts: They discharge the polluted air or smoke outside the building.
  • Fresh air inlet: Ramps, fresh air shafts or supply fans replace the extracted air. If the fresh air path is insufficient, the system will not work as designed.

Advantages over ducted systems

  • Without large ducts under the ceiling, floor height is preserved and excavation and construction costs fall.
  • Clashes with sprinklers, lighting and electrical services are largely eliminated.
  • The car park looks more open, brighter and safer.
  • Because the fans run in stages according to demand, energy consumption is lower.

Daily operation: CO control

CO detectors placed at different points in the car park measure gas levels continuously. When levels are low, the fans are off or run at low speed; when CO rises during busy hours, the fans speed up in stages. This way the car park is not ventilated at full capacity all day, energy is not wasted and fan noise is reduced.

In a fire: smoke control

When a signal comes from the fire detection system, ventilation switches to the fire scenario. The exhaust fans go to full capacity and the jet fans drive the smoke in a defined direction towards the exhaust shafts. The aim is to keep the areas outside the fire zone and the escape routes clear of smoke and to let the fire brigade approach from the side where fresh air comes in.

Fans that run in the fire scenario must therefore withstand high temperatures. Smoke extraction fans are classified according to EN 12101-3 and are selected to match the temperature and duration class required by the design (for example F300 or F400). The cables and panels supplying the fans must also be fire resistant so that the system keeps running during a fire.

Design and CFD analysis

The number, position and direction of jet fans can be estimated by hand calculation, but columns, beams, ramps and partitions in the car park strongly affect air flow. For this reason, especially in large and complex car parks, both daily ventilation and the fire scenario are modelled with CFD (computational fluid dynamics) analysis. The analysis shows whether any dead zones remain, how long smoke clearance takes and the visibility along escape routes. We bring the experience our management team gained from the CFD studies they led for tunnel and station ventilation on metro projects to car park projects as well.

Commissioning and testing

Once installation is complete, the system must be tested in both the daily and the fire scenario. Calibration of CO detectors, correct operation of fan stages through the controls, the right fans starting in the right direction on a fire alarm signal and open fresh air inlets are all verified on site one by one. The test results are reported as part of the handover file.

Conclusion

A well-designed jet fan system keeps a car park clean every day and saves lives in a fire. At Ekura, we install car park ventilation and smoke extraction systems from design through to commissioning. You can see how a basement car park with jet fans works in our 3D Residential Building tour, and learn more about our ventilation systems and mechanical contracting services.