Sprinkler systems: where are they mandatory and how are they designed?

Fire Protection14 November 2026Ekura Engineering

An automatic sprinkler system is the most effective active fire protection measure, controlling a fire before it grows. The buildings where it is mandatory and the basic rules of good design are clearly defined in the regulations.

A sprinkler system consists of heads installed at ceiling level that open automatically when heated. When a fire breaks out, only the heads above the fire open and spray water directly onto the fire zone. As a result, the fire is often controlled or extinguished before the fire brigade arrives.

Animated explainer · on-screen text in Turkish

Where are sprinklers mandatory?

Under the Turkish Regulation on Fire Protection of Buildings, sprinkler systems are mainly mandatory in:

  • All non-residential buildings taller than 30.50 m
  • Enclosed car parks with a total area above 600 m²
  • Hotels, shopping centres, warehouses and similar high-risk occupancies above certain sizes

The regulation also requires sprinkler design to follow TS EN 12845. The first step of design is therefore to determine the hazard class of the building and each of its areas correctly according to the standard.

Hazard class and design

TS EN 12845 defines light, ordinary and high hazard classes according to occupancy and fire load. Offices and dwellings are not protected in the same way as warehouses and production areas. The hazard class determines the head type, head spacing, design density, the area assumed to operate simultaneously and the volume of the water tank. The regulation requires the tank to last 30 minutes for light hazard, 60 minutes for ordinary hazard and 90 minutes for high hazard.

System components

  • Water supply and pumps: The fire water tank and fire pump set provide the required flow and pressure.
  • Control valve set: A valve assembly that isolates each zone, raises the alarm and allows testing.
  • Pipe network: Mains and branches sized by hydraulic calculation.
  • Sprinkler heads: Selected according to ceiling type, height and hazard class.
  • Flow switches and monitoring: Report to the fire detection system which zone has water flowing.

Points to watch on site

The most common problems we see on site are heads obstructed by ducts, cable trays or lighting, head positions shifting when the suspended ceiling is changed later, and insufficient pipe hangers. Sprinkler layout should therefore be coordinated with the other services. In seismic regions, the pipe network must also be seismically braced.

Testing and maintenance

After installation, the pipe network is pressure tested, valve set alarms and flow switches are tried, and the flow and pressure of the pump set are measured. In operation, checking that valves are open, regular pump run tests and making sure heads are never painted or covered are essential for reliability.

Conclusion

A correctly designed and maintained sprinkler system greatly reduces loss of life and property. At Ekura, we install sprinkler systems from hydraulic calculation to commissioning. You can explore the systems in our 3D Hotel tour and learn more about our fire systems and mechanical contracting services.