Energy · Fuel storage terminal

The hidden systemsof a tank farm.

From tank cooling to foam suppression, from product transfer to vapour recovery: the mechanical systems of a fuel storage terminal. At the end we will follow a tank fire from start to finish.

↓ Scroll down
Tank cooling rings

The tank shell is protectedby a water curtain.

The cooling ring at the top edge of each tank forms a curtain of water running down the shell. The burning tank and neighbouring tanks exposed to heat radiation are cooled; the steel shell does not weaken and the fire does not spread.

Floating roof · rim seal protection

Fires usually startat the seal.

In floating-roof tanks, most fires start in the rim seal area between the roof and the shell, often from a lightning strike. A linear heat detector along the seal detects the fire; foam pourers on the shell fill the ring between the foam dam and the shell with foam.

Fixed-roof tank · foam chambers

Foam coversthe product.

In fixed (cone) roof tanks, foam chambers at the top of the shell let foam run gently down the inside wall. The foam forms a blanket on the product surface and cuts the fuel vapour off from the air.

Bund · bund foam system

Spilled fuelstays in the bund.

The tanks stand in concrete bunds that contain any spill. Foam pourers on the bund wall cover the bund floor with foam to stop spilled fuel from igniting; the bund drain is normally kept closed.

Scenario · rim seal fire on tank T1

A tank fire,from start to finish.

Lightning strikes floating-roof tank T1 and the rim seal ignites. Follow the steps below; the scene changes at every step and the simulation restarts about every 30 seconds.

    Fire water ring main

    Uninterrupted wateraround the site.

    A ring main running around the bunds feeds the hydrants and fixed monitors. Thanks to the ring layout, water arrives from the other direction even if part of the main is shut off; monitors cool tank shells from a distance or throw foam.

    Foam concentrate and proportioner

    Foam inthe right ratio.

    Concentrate from the foam concentrate tank is mixed into the fire water at the right ratio in the proportioner. The resulting foam solution goes through the foam main to the pourers, foam chambers and bund system.

    Fire pumps and water tank

    Water arriveseven in a power cut.

    The electric main pump, a 100% standby diesel pump and the jockey pump that keeps the line under pressure are fed from the fire water tank. If the power fails, the diesel pump takes over. Because cooling in tank fires can last for hours, tank volume and pump capacity are sized accordingly.

    Transfer pumps · tank line · gas detection

    Product from the tankto the loading bay.

    Product from the tank outlet valves is pumped to the loading bay by transfer pumps. Hydrocarbon gas detectors in the pump area detect leaks early, raise the alarm and stop the pumps.

    Truck loading bay · vapour recovery

    No vapour releasedduring loading.

    Tankers are filled through bottom loading arms. Fuel vapour displaced from the tanker is sent through the vapour recovery arm to the vapour recovery unit (VRU) and turned back into liquid product. Foam-water sprinklers under the canopy protect the loading bay.

    Heavy fuel tank · steam heating

    Heavy fuelstays fluid.

    Heavy fuels such as fuel oil thicken in the cold. Steam from the boiler keeps the product at a pumpable temperature in a coil at the bottom of the tank; the insulated shell reduces heat loss and condensate returns to the boiler.

    Bund drainage and oily water separator

    Bund water never leaveswithout passing the separator.

    Rainwater collected in the bund may be contaminated with fuel. After checking, the drain valve is opened and the water is sent to the oily water separator. The separator holds back hydrocarbons and releases clean water to the sewer; firefighting water is kept under control the same way.

    Control building · pressurisation

    A safe roomon a hazardous site.

    The control building is kept at positive pressure relative to the outside, so fuel vapour cannot get in. If the gas detector at the fresh air intake detects gas, the dampers close. The air handling unit conditions the indoor air for equipment and operators.

    Fire and plant control system

    The whole siteon one screen.

    Tank levels, cooling rings, fire pumps, the foam system, the loading bay and auxiliary systems are monitored from a single screen. Choose a scenario and see how the screen and the site change.

    Installation and contracting

    Let's plan your tank farm projecttogether.

    Let's review your project together before installation; we install tank cooling, foam suppression, pumps and mechanical systems, carry out testing and commissioning, and hand them over.

    The animation shows an example fuel storage terminal; it is not to scale.