The fire pump room is the heart of sprinkler and hose systems. It must keep working even during a power cut and must be tested regularly.
A building’s fire water demand can rarely be met by the mains. The flow and pressure needed by sprinkler, hose reel and hydrant systems are provided by the fire pump set. The pump room decides whether the building’s last line of defence will work in a fire.
The pump set
A typical fire pump set has three pumps:
- Electric duty pump: Provides the system’s design flow and pressure.
- Diesel standby pump: Starts when power fails or the duty pump is faulty. It has its own fuel tank, batteries and exhaust.
- Jockey pump: This small pump makes up minor pressure losses in the network and prevents the main pumps from starting unnecessarily.
The Turkish Regulation on Fire Protection of Buildings requires an equal-capacity standby pump where a single pump is used, and, where there is no diesel standby, a reliable power supply independent of the building’s general electrical system. The shut-off head of the pumps must not exceed 140 percent of the rated head.
How does it work?
Normally the network is kept under pressure by the jockey pump. When a sprinkler head opens or a hose reel is used, the pressure drops. Below a set value the electric pump starts automatically; if pressure keeps falling or the electric pump fails, the diesel pump starts. Fire pumps start automatically but are stopped only manually, so pressure fluctuations during a fire cannot stop the pump.
Designing the pump room
- The pump room should be separated from the rest of the building by fire-resistant construction and be easily reached by the fire brigade.
- Pumps should, where possible, be fed from the tank with positive suction (below the tank water level).
- For the diesel pump, the fuel tank, spill containment, exhaust discharge and engine cooling must be planned.
- Each pump needs a test line and flow meter to measure its flow.
- Pump controllers should report running, fault and power status to the fire detection system and monitoring screen.
Testing and maintenance
Because fire pumps may stand idle for years, regular testing is vital. Running the pumps at set intervals with automatic start, checking the diesel engine’s fuel, batteries and cooling, and measuring flow through the test line should all be part of the maintenance programme. A pump that is not tested cannot be relied upon in a fire.
Conclusion
With the right pumps, a reliable power supply, correct controls and regular testing, a fire pump room becomes a real safeguard. At Ekura, we deliver fire pump rooms on a turnkey basis. You can see a pump room with electric, diesel and jockey pumps in our 3D Logistics Warehouse tour and learn more about our fire systems.