Most deaths in fires are caused by smoke, not flames. Pressurising escape stairs lets people leave the building by a smoke-free route.
In tall buildings, lifts are not used during a fire; people leave by the escape stairs. If smoke enters these stairs, the escape route becomes unusable. A stair pressurisation system blows fresh air into the stairwell, keeping its pressure higher than the floor corridors and preventing smoke from entering.
Where is it required?
The Turkish Regulation on Fire Protection of Buildings requires pressurisation in buildings taller than 51.50 m and for escape stairs serving more than four basement levels. In some lower buildings, stairs must also be naturally or mechanically ventilated or pressurised.
Key values in the regulation
- With all doors closed, the pressure difference between the pressurised stair and the occupied areas must be at least 50 Pa.
- With doors open, a pressure difference of at least 15 Pa must be maintained.
- The force needed at the door handle to open the door must not exceed 110 N.
- With each door fully open, the average air velocity through the door must be at least 1 m/s.
These values balance two goals: the pressure must be high enough to keep smoke out, but low enough not to make the door hard to open.
How does the system work?
The pressurisation fan takes fresh air, usually from the roof or ground level, and distributes it through a shaft to different levels of the stair. As doors open and close, the pressure in the stair changes. Two common methods keep the pressure stable:
- Variable-speed fan: Continuously adjusts fan speed based on a pressure sensor signal.
- Pressure relief damper: Releases excess air when the pressure rises too high.
The system starts automatically on a signal from the fire detection system or a manual call point. The fan and its panel are supplied through fire-resistant cables so that power is not lost during a fire.
Other smoke control systems
Stair pressurisation is part of the building’s smoke control strategy. Lift shaft pressurisation, smoke extraction in corridors and atria, jet fan systems in car parks and smoke dampers work together. A fire scenario matrix should be prepared and tested through the controls so that all these systems start in the right order.
Testing and commissioning
During commissioning, pressure differences with doors closed and open, door opening forces and air velocities at doors are measured, and fans and dampers are verified to respond correctly to the fire signal. The measurements are reported and presented at fire brigade acceptance.
Conclusion
A pressurisation system is a silent safeguard that lets people evacuate safely in a fire. At Ekura, we install stair and lift pressurisation and smoke extraction systems from design review to commissioning. You can explore these systems in our 3D Hospital tour and learn more about our ventilation systems.